16
6.7.3 The requirements of defrosting operation:
1.
Sleep indicator flickers at the speed of 1 time per second
2.
When defrosting operation starts, the compressor and indoor fan
will stop working while outdoor fan and four-way valve will
continue to work.
3.
The four-way valve and outdoor fan will stop operating in 30
seconds.
4.
15 seconds after that, the compressor starts and goes into
defrosting operation.
5.
After the defrosting ends, the compressor stops working. And
the four-way valve and outdoor fan begins to work in 20
seconds.
6.
20 seconds after that, the compressor starts and goes into heating
operation. And the indoor fan enters into the prevention mode of
cold wind.
6.8
Auxiliary electric heating function
6.8.1
Only if the following conditions are satisfied under the
heating operation, can the auxiliary electric heating go into
operation automatically.
a.
The compressor works for 4 minutes by heating pump
b.
Indoor temperature is less than 22 ;
c.
The temperature set-indoor temperature is more than 3 ;
Summary of Contents for ASW-07B4/HSAR
Page 1: ......
Page 7: ...Operation Hints ...
Page 8: ......
Page 9: ......
Page 33: ......
Page 35: ...Chapter 5 Main Technical Data ...
Page 42: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Page 61: ...Operation Hints ...
Page 62: ......
Page 63: ......
Page 93: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Page 112: ...6 60 detachable cool warm type 70 detachable cool warm type ...
Page 113: ...7 Operation Hints ...
Page 114: ...8 ...
Page 146: ...40 4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...