6 Installation and network wiring
© Copyright Reserved Autonics Co., Ltd.
27
(2)
Network power
Network power is 24VDC. It is also available for power of ARD(analog) remote I/O.
You must use separate power for network power and I/O contact.
If using same power, it may cause network problem.
(3)
Terminating resistance
120
Ω
, 1% of metallic film, 1/4W
Do not install terminating resistances at ARD unit. If installing them at ARD unit, it may
cause network problem. (impedance can be too high or low. )
Connect terminating resistance on the both ends of the trunk line.
(4)
Tap(selectable)
It is convenience to use taps for wiring network between ARD units at several places.
Multi-drop wiring
Wiring using Taps
(5)
Connector wiring
Wiring using a tap: Connect two connectors at a tap.
Multi-drop wiring: Connect two cables to one connector (accessory)
Summary of Contents for ARD Series
Page 1: ... Copyright Reserved Autonics Co Ltd iii USER MANUAL ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 9: ...1 Product overview Copyright Reserved Autonics Co Ltd 9 ...
Page 13: ...1 Product overview Copyright Reserved Autonics Co Ltd 13 ...
Page 16: ...3 Dimensions 16 Copyright Reserved Konics Co Ltd 3 Dimensions unit mm Panel cut out ...
Page 17: ...3 Dimensions Copyright Reserved Autonics Co Ltd 17 ...
Page 29: ...6 Installation and network wiring Copyright Reserved Autonics Co Ltd 29 ...
Page 81: ...8 Unit parameter setting Copyright Reserved Autonics Co Ltd 81 ARD AO04 ...
Page 103: ...9 DeviceNet Explicit Message Copyright Reserved Autonics Co Ltd 103 ...
Page 113: ...10 Parameter Copyright Reserved Autonics Co Ltd 113 MOO ARDAU1 V1 0 1303US ...