5 I/O data of DeviceNet analog unit
22
© Copyright Reserved Konics Co., Ltd.
5.2
Current range of analog I/O unit
(1)
Current input range: DC 4 to 20 mA
For 4 to 20mA of current range, analog data has the value of 0x0000 to 0x3E80(0 to 16,000).
Max. allowable input range is 3.2 to 20.8mA and that of analog data is able to convert as
0xFCE0 to 0x41A0(-800 to 16,800).
(2)
Current input range: DC 0 to 20 mA
For 0 to 20mA of current range, analog data has the value of 0x0000 to 0x3E80(0 to 16,000).
Max. allowable input range is 0 to 21mA and that of analog data is able to convert as 0x
FCE0 to 0x41A0(-800 to 16,800).