8 Unit parameter setting
© Copyright Reserved Autonics Co., Ltd.
93
8.4.7
CH
□
Moving Average Filter of Number
This function is used for vibrated or vacillated input value which has noise.
This parameter is available when Moving Avarage is selected at CH
□
Function Choice. Refer to
the ‘8.3.6 CH
Set range: Moving Average No_2
↔
Moving Average No_4
↔
Moving Average No_8
↔
Moving Average No_16
↔
Moving Average No_32
↔
Moving Average No_64
↔
Moving
Average No_128
↔
Moving Average No_256
Factory default: Moving Average No_8
When setting as Moving Average No_32, it operates 32 times of samplings and displays ‘ the
value/32’.