Characteristic

l

2 monitored digital input

l

Input lines are monitored for open line and short/open circuit (terminal resistors is
mandatory)

l

Microprocessor-controlled signal evaluation

l

Prevention of noise interference through intelligent analysis of input signals

l

LED display of input status

l

Automatic address setting, without encoder settings or Dip-switch

l

Power supply via FD18-BUS

l

Communication with controller via FD18-BUS(detection line)

l

Directly used in dry areas, Applicable in dusty and humid areas when installed in
FDCH221 housing

l

“Sticker Method” easy for commissioning

Application

With the input a status can be monitored, the input can be configured by controller or
configuration tools as follows:

l

Status

 input or

Alarm

 input

l

Lead monitoring for open line or open line and short circuit

l

When inputting status, according to different status of contact, can be set as

follows:

-

Normal mode: normally open input

-

Inverted mode: normally closed input

Summary of Contents for FDCI181-2

Page 1: ...er settings or Dip switch l Power supply via FD18 BUS l Communication with controller via FD18 BUS detection line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application With the input a status can be monitored the input can be configured by controller or configuration tools as follows l Status input or ...

Page 2: ...e potential free Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the status of the inputs The cover of the printed circuit board is transparent so that the state of the LEDs is visible even when the housing is closed To protect the modules from environmental influences the...

Page 3: ...oles 182 0 1 0mm 4 Fix and guide in the cables with waterproof joint provided by users themselves 5 Fix the lid additionally with four screws Fig 4 Only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Installation of module in FDCH221 housing Caution Overheating of FDCI1...

Page 4: ... 28 mA Activation current 0 52 mA Monitoring resistors 3 3KΩ 1 4w 680Ω 1 4w Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With housing FDCH221 IP65 Approval for Russian TR RF N123 FZ Details for ordering T...