Preparation

Determine the type of installation: there are 2 types of
installation for FDCI181-2 Input module:

Installation outside a switching cabinet or a control unit:
use FDCH221 housing (Fig. 3) .

Installation directly in a switching cabinet or a control
unit: mount the module on an even surface (Fig.2).

Damage by water!

In humid or wet environments always use the housing
FDCH221!

Installation of FDCH221 Housing

1.

Open the housing.

2.

Determine the cable entries in the housing and break
these open.

3.

Use two screws (M 4) to fit the housing on a plane
surface (Fig. 3). Distance between holes: 182.0

±

1.0mm.

4.

Fix and guide in the cables with waterproof joint
(provided by users themselves).

5.

Fix the lid additionally with four screws (Fig. 4). (Only this
way is IP65 protection guaranteed.)

The housing lid is transparent. Consider a suitable
installation position to make sure that the LEDs of the
module are visible at any time.

Installation of module in FDCH221 housing

Caution!

Overheating of FDCI181-2 input module.

1.

Open the housing.

2.

Fix module with two screws in the housing (Fig. 3).

3.

Close the housing.

Installation on an even surface

1.

Position module on an even surface (Fig. 2).

2.

Fix module with two M4 screws. Distance between
holes:63.5

±

1.0mm.

Electric connection

1.

Connect the cables to the terminals according to Fig.
5/6.

Connect only one wire per terminal!

2.

Connect the resistors to the end of the monitored line.

2 resistors of 3.3K

Ω

and 2 of 680

Ω

are delivered with

the product.

Summary of Contents for FDCI181-2

Page 1: ...er settings or Dip switch l Power supply via FD18 BUS l Communication with controller via FD18 BUS detection line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application With the input a status can be monitored the input can be configured by controller or configuration tools as follows l Status input or ...

Page 2: ...e potential free Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the status of the inputs The cover of the printed circuit board is transparent so that the state of the LEDs is visible even when the housing is closed To protect the modules from environmental influences the...

Page 3: ...oles 182 0 1 0mm 4 Fix and guide in the cables with waterproof joint provided by users themselves 5 Fix the lid additionally with four screws Fig 4 Only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Installation of module in FDCH221 housing Caution Overheating of FDCI1...

Page 4: ... 28 mA Activation current 0 52 mA Monitoring resistors 3 3KΩ 1 4w 680Ω 1 4w Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With housing FDCH221 IP65 Approval for Russian TR RF N123 FZ Details for ordering T...

Reviews: