Owner Installation Instructions
Easy Slider - Sliding Gate Opener
23
Menu 4. Lock times
Lock output can be programmed for both hold and pulse motor starting. The operation of the lock can be
programmed to operation and can also be programmed to activate prior to the gate behave differently on open
cycle to that on close cycles.
Control board adjustments
Parameter
Min
Max
Default
Step
Unit
Menu No.
OPEN LOCK TIME Set the time the lock is
activated for on open cycles
0.0
Hold
0.5
0.1
Sec
4
CLOSE LOCK TIME Set the time the lock is
activated for on close cycles
0.0
Hold
0.5
0.1
Sec
4
PRE-OPEN LOCK TIME
Time the lock is activated for prior to opening
0.0
25.5
0.0
0.1
Sec
4
PRE-CLOSE LOCK TIME
Time the lock is activated for prior to closing
0.0
25.5
0.0
0.1
Sec
4
Menu 5. Light times
With the addition of a relay module connected to the control activated for prior to a drive cycle. This is used
to warn that gate board, a light can be controlled. The time the light stays on, is movement is pending. The
second times how long the light controlled by two timers. The first times the period the light is remains on after
a cycle. The parameters are shown below.
Parameter
Min
Max
Default
Step
Unit
Menu No.
ON AFTER CYCLE LIGHT TIME
Time light remains on for after a cycle
0
255
60
1
Sec
5
ON BEFORE OPEN CYCLE LIGHT TIME
Minimum time light is activated for prior to
opening
0
255
0
1
Sec
5
ON BEFORE CLOSE CYCLE LIGHT TIME
Minimum time light is activated for prior to
closing
0
255
0
1
Sec
5
Menu 6. Motor settings
Motor speed
The maximum speed the motors run at is controlled by the MOTOR FULL SPEED VOLTAGE parameter. The
default value is the maximum recommended for normal operation. If however the gates move too quickly
for a particular installation the voltage can be reduced to make the motors run slower.
NOTE:
Altering these
parameters will cause the travel limits to be cleared.
Gate leaf synchronising delays
These parameters determine the minimum distance that is maintained between the gates leaves when leaving
or approaching the closed position. If the speed of the gates differs considerably then an extra delay can be
introduced. The units used are revolutions of the drive pinion gear.
NOTE:
altering these parameters will cause
the travels limits to be cleared.
Parameter
Min
Max
Default
Step
Unit
Menu No.
MOTOR FULL SPEED VOLTAGE
Sets the full speed motor voltage
~12.1
~22
~20
~1
Volts
6
GATE LEAF SYNCHRONISING DELAY
Sets the # of turns delay between gates opening
1
5
2
1
Revs
6
EXTRA SYNCHRONISING DELAY FOR CLOSE
Additional # turns delay between gates opening
0
5
1
1
Revs
6
Control board adjustments