background image

LIMIT SWITCH / AMP TRAVEL SETUP (cont)

STEP 3. CONFIRMING CORRECT WIRING DETECTED

The controller will now automatically detect the type of drive unit
used by the number of wires used. If the correct number of wires
is displayed then press SET to continue otherwise press EXIT and
check the wiring. 

Continue from STEP 4A for 2WIRE (AMP TRAVEL) Setup.

STEP 4. CONFIRMING MOTORS DETECTED.

The controller will now automatically detect if one or two motor
are connected. If the correct number is displayed then press SET
to confirm otherwise press EXIT and check the wiring.

STEP 5. ADJUSTING CLOSE LIMIT(S).

The controller will now prompt for the motor(s) to be driven to the
desired close limit and for the limit switches to be adjusted so that
the motor stops at the desired position. The motor can be driven
using the UP and DOWN buttons on the console keypad or Button
1 and 4 of a transmitter. After making adjustments to the limit
switch positions always re-approach the limit at full speed by

driving the motor open a short distance and then driving it close
again. When the close limit has been adjusted press SET to con-
tinue. Note: If the motor drives in the wrong direction (UP closes
gate / DOWN opens gate) the motor wires need to be swapped. 

STEP 6. ADJUSTING OPEN LIMIT(S).

The controller will now prompt for the motor(s) to be driven to the
desired open limit and for the limit switches to be adjusted so that
the motor stops at the desired position. The motor can be driven
using the UP and DOWN buttons on the console keypad or Button
1 and 4 of a transmitter. After making adjustments to the limit
switch positions always re-approach the limit at full speed by
driving the motor close a short distance and then driving it open
again. When the open limit has been adjusted press SET.

STEP 7. AUTOMATIC PROFILING

After a brief pause the controller will automatically close and
open gate several times and learn the gates load and travel 
characteristics. When the setup is complete the MAIN SCREEN
will be displayed with the gate shown to be OPEN. The Gate can
now be used.

/

/\

\\

\/

 

M1(2)& 

 Adjust

CLOSE 

 Limit, 

 

SET

 

PRESS 

Adjusting The CLOSE LIMIT

OR

 

PRESS 

8

 

PRESS 

Confirming Detected Motor Wiring

Motor 

 =2/3/5 

 Wire

Press 

 SET 

 if 

 OK

 

PRESS 

Confirming Detected Motor Wiring

M1&2 

 Detected|

Press 

 SET 

 if 

 Ok.

/

/\

\\

\/

 

M1(2)& 

 Adjust

OPEN 

 Limit, 

 

SET

 

PRESS 

Adjusting The OPEN LIMIT

OR

 

PRESS 

AMP TRAVEL SETUP (Step 4A)

STEP 4A. SELECTING THE NUMBER OF MOTORS.

The controller will now prompt for the number of motors con-

nected to be entered. Use the UP or DOWN key to select the cor-
rect number and then press SET.

STEP 5A. TEST AND ADJUST STOP DETECTION CUR-
RENT TRIP LEVELS.

Note: If a dual gate installation is being used, steps 5A and 6A
will be undertaken for motor 2 and then motor 1.
For this type of installation the controller detects the travel limits
by sensing a motor current trip when the mechanical stop is
reached.. In this step, the stop detection current trip levels for each
motor are tested and adjustments made to obtain the optimum
level. A high value results in undue force, while a low value will
result in the gate stopping midway due to variations in friction etc. 
continued...

 

PRESS 

Selecting Number Of Motors Used

Select 

 Number 

 of

Motors 

  

  

  

  

  

  

  

  

 1

1

Summary of Contents for CB-19

Page 1: ...COPY Warning Failure to comply with the installation instructions and the safety warnings may result in serious personal injury and or property opener or controller damage Installation Instructions C...

Page 2: ...GARAGE DOOR OPENERS GATE OPENERS REMOTE CONTROL ACCESS SOLUTIONS...

Page 3: ...ING UP THE CONTROLLER 7 SETUP TRAVEL 7 LIMIT SWITCH AMP TRAVEL SETUP 9 RE PROFILING TRAVEL 10 SETTING TIMED TRAVEL 11 SETTING PEDESTRIAN POSITION 12 DESCRIPTION OF STANDARD OPERATION 13 CONTROL BOARD...

Page 4: ...d for the installer to touch any console buttons during the coding process When all transmitters are coded a trans mitter storage report can be generated which can be easily transferred to a P C for r...

Page 5: ...al 2 16 MOTOR 2 close limit switch input terminal 17 MOTOR 2 open limit switch input terminal 18 COM terminal for Terminals 16 17 19 20 19 MOTOR 1 close limit switch input terminal 20 MOTOR 1 open lim...

Page 6: ...ansmitter Testing See Page 23 Event History Display See Page 23 Memory Usage See Page 23 Periodic Service Cycle Counter See Page 24 Parameter List 1 Open Lock Time 2 Close Lock Time 3 Pre Opn Lock Tim...

Page 7: ...NG CONTROL SWITCH INPUTS When remote control operation is only required the CB 19 s con trol switch inputs are not utilised It is however strongly advised that a Photo electric Safety Beam be used to...

Page 8: ...borted at anytime by pressing EXIT STEP 1 NAVIGATING TO LIMIT AMP TRAVEL MENU To navigate to the Menu 10 1 from the MAIN SCREEN simply press PREVto display MENU 10 followed by SET to display MENU 10 1...

Page 9: ...console keypad or Button 1 and 4 of a transmitter After making adjustments to the limit switch positions always re approach the limit at full speed by driving the motor close a short distance and then...

Page 10: ...lly close and open gate several times and learn the gates load and travel characteristics When the setup is complete the MAIN SCREEN will be displayed with the gate shown to be OPEN The Gate can now b...

Page 11: ...g up the travel times The first allows the installer to drive the motor s so that the actual travel time can be recorded The second allows exact times to be entered Note The limit setting procedure ca...

Page 12: ...me Save Settings PRESS Confirming Settings SETTING TIMED TRAVEL ENTER TIMES STEP 5A ENTERING TIMED TRAVEL PARAMETERS When the ENTER TIMES method is selected a list of parameters is provided to configu...

Page 13: ...Activated by PED terminal with N O switch or by transmitter button with PED Function assigned The pedestrian access operation partly opens the gate to allow pedestrian access but prevent vehicle acce...

Page 14: ...pplies 0 1 25 5 1 0 0 1 SEC 2 AMP TRIP LIMIT Motor drive electronics current limit 0 13 13 1 AMPS 2 PARAMETER AMP LIMITS MIN MAX DEFAULT STEP UNITS MENU MOTOR 1 OPEN LIMIT AMPS Sets Motor 1 open limit...

Page 15: ...tions for safety reasons A P E beam must be used for these features to be activated AUTO CLOSE AFTER POWER UP Auto close after power up is normally not enabled for safety rea sons but can be enabled i...

Page 16: ...configured to a SWIPE type input for pedestrian access This provides full functionality with the P E Triggered Pedestrian auto close function REMOTE CODE The controller supports the Remote Code Set fe...

Page 17: ...input is used to alter the P E trig gered auto close feature so that P E triggered auto close is only initiated when the gateway is exited The direction of travel is determined by the sequence in whi...

Page 18: ...yed Using the NEXT PREV buttons step through the list of parameters until the required parameter is displayed If the parameter s value is not to be changed then skip to step 7 when finished viewing th...

Page 19: ...ode Transmitter menu will now be shown Press EXIT to return to the MAIN SCREEN and test the transmitter MENU 1 Code Transmitter PRESS Starting Code Transmitter Procedure Press Tx er Button LIST Press...

Page 20: ...cheme which ties the store location to the transmitter s owner STEP 5 SELECTION OF ID OR SN DISPLAY When the cursor is moved to the ID SN indicator the UP and DOWN buttons toggle between displaying th...

Page 21: ...tter s location within the list NOTE VIEW will not be shown if the transmitter is not stored 20 THE CONTROLLER PROVIDES A TRANSMITTER LISTING FACILITY WHICH ENABLES THE USER TO FIND A TRANSMITTER LOCA...

Page 22: ...code operation is selected for a location that already contains a transmitter then the BASIC CODE TRANSMITTER PROCEDURE will be initiated and the new transmitter will replace the existing one Note tha...

Page 23: ...for 2 seconds The example shows Button 1 being used but it could be any button It can even be an unused button on the existing transmitter STEP 5 CONFIRM TRANSMITTER BUTTON TO BE CODED Within 10 seco...

Page 24: ...be displayed that shows the transmitter details along with the button pressed The example below shows the case when transmitter number 124 is activated by button 4 Note ID is selected for display MENU...

Page 25: ...1234 When finished viewing simply press EXIT 24 Viewing Service Counter Service Counter CYCLES 60000 Viewing Counters 1 Open Cycles 1234 1 Open Cycles 2 Close Cycles 3 Ped Cycles 4 Warranty Cycles 5...

Page 26: ...VAC 24VAC 30VDC 5AMPS RECEIVER TYPE UHF 433 92 MHz AM Receiver RECEIVER CODE STORAGE CAPACITY 30 x 4 Button Transmitter Codes TRANSMITTER FREQUENCY 433 92 MHz CODING TYPE Hopping Code No of CODE COMBI...

Page 27: ...aims any liability of whatsoever nature in respect of any claim or demand loss or damage which arise out of a accidental damage to or normal wear and tear to the Product or to the Product s components...

Page 28: ...GARAGE DOOR OPENERS GATE OPENERS REMOTE CONTROL ACCESS SOLUTIONS...

Reviews: