11
Press EXIT if the gate is not open and the controller will now
prompt for the gate to be opened by holding the UP key. When the
UP key is released the motor(s) will stop and STEP 6 restarted.
Note: If the motor drives in the wrong direction the motor wiring
needs to be swapped.
STEP 7. SETTING CLOSE CYCLE DRIVE TIME.
The controller is now ready for the close cycle drive time to be set.
To do this simply press and hold the DOWN key until the gate is
driven fully closed. Note: If the motor drives in the wrong direc-
tion the motor wiring needs to be swapped.
STEP 8. SETTING OPEN CYCLE DRIVE TIME.
The controller is now ready for the open cycle drive time to be set.
To do this simply press and hold the UP key until the gate is driv-
en fully open.
STEP 9. CONFIRMING SETTINGS.
The controller will now prompt you to save the settings. Press
EXIT to restart from STEP 6 or, if you are happy with the settings
press SET and the main screen with be displayed and the gate is
ready to be used.
SETTING TIMED TRAVEL - DRIVE MOTORS (cont)
Hold
/
/\
\
until
gates
Are
Open!
PRESS
Opening Gate in Preparation For Setting Travel Times
Hold
\
\/
/
to
set
close
cycle
time
PRESS
Setting Close Cycle Time
Hold
/
/\
\
to
set
open
cycle
time
PRESS
Setting Open Cycle Time
Save
Settings?
PRESS
Confirming Settings
SETTING TIMED TRAVEL - ENTER TIMES
STEP 5A. ENTERING TIMED TRAVEL PARAMETERS.
When the ENTER TIMES method is selected a list of parameters
is provided to configure the gates travel. The parameters provid-
ed are listed below with a brief discription.
M1 Normal Open Time
-Sets Open drive time for M1
M1 Normal Close Time
-Sets Close drive time for M1
M2 Normal Open Time
-Sets Open drive time for M2*
M2 Normal Close Time
-Sets Close drive time for M2*
Close Sync Delay
-Sets Delay before M1 is started on
close cycles*
Open Sync Delay
-Sets Delay before M2 is started on
open cycles*
*Only used for dual gate installations.
Once the parameter values have be set press EXIT and the main
screen is displayed and the gate is ready for use.
SETTING PEDESTRIAN ACCESS POSITION
The controller can be instructed, via its pedestrain control feature,
to partly open and provide pedestrian access but prevent vechilar
access. This is acheived by partly opening the motor 1 gate leaf.
If daul motors are used, motor 2’s gate leaf is held closed. The
partly open position of motor 1’s gate leaf is initally set to a posi-
tion halfway between open and closed. This initail position can be
adjusted by the installer to any postion within the gates travel
range by selecting a pedestrian access travel time (from closed).
The setting is accessed from “MENU 10.4 Set Pedestrian”. The
time is adjustable in 1 second steps.