15
CONTROL BOARD ADJUSTMENTS (cont)
The motor settings adjust various aspects of the gate travel. When
a single gate installation is used the SYNC DELAY TIMES and
M2 settings are ignored. The default value for the CLOSE SYNC
DELAY
time is automatically calculated for LIMIT
SWITCH/AMP TRAVEL installations. The value calculated is
selected so that the delay between M2 and M1 reaching the close
position is equal to the OPEN SYNC DELAY TIME. The MAX
OVERRUN TIME is set to 0 for TIMED TRAVEL installations.
MENU 5 LIGHT TIMES
MENU 6 MOTOR SETTINGS
The control board’s light function can be programmed to operate
a courtesy light or a warning light. The time the light stays on for
after a cycle is adjustable. The light can also be activated prior to
the gate moving so that a warning can be given of the pending
movement.g. Note the light outoput can be selected to be either
OUTPUT1 or OUTPUT2. The parameters are shown below.
MENU 7 OPERATING MODES
P.E INPUT RESPONSE MODE
The P.E input can be configured to respond in one of three modes.
OPEN AND CLOSE CYCLES STOP - In this mode all
cycles are prevented from being completed or initiated when the
P.E input is active.
CLOSE CYCLES STOP - In this mode the P.E input has
no effect when opening but will stop the gate when closing.
REVERSES CLOSE CYCLES - In this mode the P.E
input has no effect when opening but will cause the gate to reverse
if activated when closing.
PED INPUT FUNCTION
The PED input can be configured to a SWIPE type input for
pedestrian access. This provides full functionality with the P.E
Triggered Pedestrian auto-close function.
REMOTE CODE
The controller supports the Remote Code Set feature. This
parameter can be used to disable the feature for security or
transmitter management reasons.
ACTIVITY REPORTS & ACTIVITY REPORT ID
This parameter selects an activity report output. The ID number
is used to select the ID of the controller. Contact ATA for more
details
PARAMETER
MIN
MAX
DEFAULT STEP UNITS
MENU #
CLOSE SYNC DELAY TIME
Time delay between M2 and M1 closing
0.0
25.5
Auto (2.0) 0.1
SEC
6
OPEN SYNC DELAY TIME
Time delay between M1 and M2 opening
0.0
25.5
2.0
0.1
SEC
6
OPEN SPEED VOLTS
Voltage applied to motors when opening
12
24
22
1
VOLTS
6
CLOSE SPEED VOLTS
Voltage applied to motors when closing
12
24
20
1
VOLTS
6
STOP PAUSE TIME
Pause time used between motor direction changes
0.0
2.0
0.2
0.1
SEC
6
M1 NORMAL OPEN TIME
Normal open time for motor 1
0.0
60.0
0.0
0.1
SEC
6
M1 NORMAL CLOSE TIME
Normal close time for motor 1
0.0
60.0
0.0
0.1
SEC
6
M2 NORMAL OPEN TIME
Normal open time for motor 2
0.0
60.0
0.0
0.1
SEC
6
M2 NORMAL CLOSE TIME
Normal close time for motor 2
0.0
60.0
0.0
0.1
SEC
6
MAX OVERRUN TIME
Extra time allowed for cycle to complete (beyond
normal cycle time)
0
60
5 (0)
1
SEC
6
PARAMETER
MIN
MAX
DEFAULT STEP UNITS
MENU #
ON AFTER CYCLE LIGHT TIME
Time light remains on for after a cycle
0
255
60
1
SEC
5
ON BEFORE OPEN CYCLE LIGHT TIME
Minimum time light is activated for prior to opening
0
255
0
1
SEC
5
ON BEFORE CLOSE CYCLE LIGHT TIME
Minimum time light is activated for prior to closing
0
25.5
0
1
SEC
5