Owner Installation Instructions
Axess® Pro Series 3000
25
The standard operation of the opener can be altered by editing various parameters. This section
describes the parameters and the effect they have. Use the VIEWING AND EDITING PARAMETER
PROCEDURE on Page 16 to make changes.
Menu 2.0 Current Trips
Motor overload detection is provided to protect the door and the opener. The motor is designed to run with
full load current. With the default values The opener will run with 7.4 Amps for 10 seconds before going into
overload.
Parameter
Min
Max
Default
Step
Unit
Menu No.
Full Load Bus Amps
0.0
3.7
3.7
1
Amps
2.1
100% Overload Time
0
30
10
1
Sec
2.2
Control Board Adjustments
Menu 3. Auto-Close Times
The Auto-Close modes automatically close the door
after it has been operated. To implement this, the
controller starts a timer once the door has reached its
desired open position. The timer then counts down
and when it expires, the controller starts to close the
door. Details about the four Auto-Close modes follow.
Automatic Technology strongly recommend using a PE
Beam for added safety.
Standard Auto-Close
This mode is selected by entering a non-zero time for
the
STD Auto-Close
parameter. When selected the
door will Auto-Close after being fully opened (except
when the door has reversed to the open position
after a motor obstruction or overload). Countdown
is suspended by: the P.E, OPN or SWP input being
active. The countdown is aborted if the STP input is
activated. If the door is already open and the OPN or
the SWP input is activated, then the countdown will
start.
P.E triggered Auto-Close
This mode is selected by entering a non-zero time for
the
“P.E Auto-Close”
parameter. This mode is used
to Auto-Close the door but only after a vehicle has
passed through the doorway and triggered the P.E
input. The swipe input can be used to clear the P.E
triggered status so that the P.E input must be
activated again before the countdown will start.
As with the other P.E modes the STP input will
abort countdown and the OPN and SWP inputs
will restart the countdown if the door is OPEN.
Pedestrian access Auto-Close
This mode is selected by entering a non-zero
time for the
“Ped’n A/C”
parameter. When
selected the door will Auto-Close after being
opened for pedestrian access unless it was
following a reverse from an obstruction.
P.E triggered pedestrian Auto-Close
This mode is selected by entering a non-zero
time for the
“P.E Ped’n A/C”
parameter.
This mode is the same as the P.E triggered
Auto-Close mode but it only operates during
pedestrian access. As the SWP input is not
available during pedestrian access, the PED
input can be confi gured to act in a SWP mode
by setting the
“PED I/P = PED SWIPE MODE”
parameter to
ON.
Auto-Close after obstruction
Two parameters are provided to enable the Auto-
Close feature to be activated after obstructions.
Normally the Auto-Close feature is not enabled
after obstructions for safety reasons. A P.E beam
must be used for these features to be activated.