![AUTOFLAME Mini Mk8 M.M. Installation And Commissioning Manual Download Page 74](http://html1.mh-extra.com/html/autoflame/mini-mk8-m-m/mini-mk8-m-m_installation-and-commissioning-manual_3021294074.webp)
74
当使用任意值数据时,我们建议用以下方法来计算和设置
10
个点的热值。
For example: Burner Rating: 5.4MW; Turndown Ratio: 5:1.
例如:燃烧器规格:
5.4MW
,调节比:
5:1
Giving the range (5.40, 4.92, 4.44, 3.96, 3.48, 3.00, 2.52, 2.04, 1.56, 1.08)
根据燃烧器规格,
10
个设定点应为
(5.40, 4.92, 4.44, 3.96, 3.48, 3.00, 2.52, 2.04, 1.56, 1.08)
Fuel flow metering serves to totalise the amount of fuel being used at each position. If any changes
are made to the curve through Single Point Change, then fuel flow will need to be re-commissioned.
燃料流量表被用来计量各个设定位的燃料总用量。如果通过“单点更改”改变了燃烧曲线
,
那
么必需重新调试燃料流量。
Fuel flow commissioning set by option 57, and is carried out in Run mode. The burner must be firing.
在选项
57
中启用燃料流量表,然后在系统运行模式下调试燃料流量表。这时燃烧器必须燃烧。
On the Home Screen, press
to access the System Configuration screen.
在控制模块主页上按下
按钮来进入系统配置屏幕。