![AUTOFLAME Mini Mk8 M.M. Installation And Commissioning Manual Download Page 25](http://html1.mh-extra.com/html/autoflame/mini-mk8-m-m/mini-mk8-m-m_installation-and-commissioning-manual_3021294025.webp)
25
2
Burner on/off enabled and setpoint control disabled.
允许用户控制燃烧器启停,但是关闭设定点控制。
3
Burner on/off and setpoint control enabled.
允许用户控制燃烧器,允许用户控制设定点
16
0
Sequencing and D.T.I Enable:
A lead boiler can be selected by press Lead Boiler in
the IBS screen or via the D.T.I. if optioned. Only 1 M.M. may be selected as lead
boiler at a time, or the sequencing will not operate. The Lead Boiler button on the
M.M. overrides the D.T.I. Lead Boiler Select.
排序和
DTI:
在锅炉智能排序界面(
IBS
)选择领头锅炉或者通过
D.T.I.
远程选择
领头锅炉。每次只有一个控制模块(锅炉)能被选为领头锅炉,否则排序无法
进行。本地控制模块的领头锅炉按钮要优先于
D.T.I.
远程选择的领头锅炉。
0
Sequencing disabled.
关闭排序
1
Sequencing enabled.
开启排序
2
D.T.I. enabled.
开启
D.T.I.
3
Sequencing and D.T.I.
开启排序和
D.T.I.
Note:
Accurate fuel flow metering must be entered for sequencing of different
burner ratings, as fuel flow metering high fire point sets the burner rating.
注意:必须安装准确的燃料流量表来实现不同规格的燃烧器排序。燃料流量表
的大火位与燃烧器规格对应。
17
0
Unused.
未使用
18
1
Carry Forward of Trim:
When the system modulates, the correction that may
already exist on the air damper position can be carried forward. This option is only
relevant if an E.G.A. is operational on the system. Trim will be reset if the rate of
change of the fuel valve angle is greater than that set in parameter 14.
EGA
调节值的延续:当系统进行控制时,已有的空气挡板调节值将得以延续。
该选项只在
E.G.A.
运行时才有效。当燃料阀门角度变化速率大于参数
14
的数值
时,空气挡板调节值将被重置。
0
Disabled.
关闭选项
1
Enabled.
启用选项
19
0
O
2
Upper Limit Offset:
This is an offset limit from the commissioned values.
Options 19 - 27 are only relevant if an E.G.A. is operational on the system. Option
12 must be set to 3.
氧气上限补偿值:这是调试值的补偿值极限。选项
19 – 27
只在
E.G.A.
处于运行
时才有效。选项
12
的数值必须是
3
。
0
Disabled.
关闭选项
0.1 -
10.0
% O
2
氧气百分比
20
0
CO
2
Upper Limit Offset:
This is an offset limit from the commissioned values.
二氧化碳上限补偿值:这是调试值的补偿值极限。
0
Disabled.
关闭选项
0.1 -
10.0
% CO
2
二氧化碳百分比
21
0
CO Upper Limit Offset:
This is an offset limit from the commissioned values.
一氧化碳上限补偿值:这是调试值的补偿值极限。
0
Disbaled.
关闭选项
1 - 200
ppm CO
一氧化碳百万分率
22
0
O
2
Lower Limit Offset:
This is an offset limit from the commissioned values.
氧气下限补偿值:这是调试值的补偿值极限。
0
Disabled
Summary of Contents for Mini Mk8 M.M.
Page 1: ...1...
Page 6: ...6 1 1 Mini Mk8 M M MK8 1 1 1 Fixing Holes and Dimensions...
Page 7: ...7 1 2 Wiring Schematic...
Page 8: ...8...
Page 15: ...15 1 4 Connection Between Mini Mk8 M M and Mk8 E G A Mk8 Mk8 E G A...
Page 16: ...16 1 5 Connection Between Mini Mk8 M M and Mk7 D T I Mk8 Mk7 D T I...
Page 17: ...17 1 6 Sequencing Connection Diagram Mk8...
Page 53: ...53 3 3 3 Servomotors Direction Change...
Page 122: ...122 Notes...
Page 123: ...123...
Page 124: ...124...