5
RWA Control Unit
LSF 7000
01
P
reliminary
r
emarks
/ s
afety
i
nstruCtions
s
Afety
i
nstructions
!
W
Arning
It is important to follow these instruc-
tions for the safety of all persons. These
instructions should be stored carefully for
the entire life cycle of the products.
Danger of crushing or entrapment!
Windows operated by electric can
close automatically!
The compressive force is sufficient to
crush fingers when careless.
Area of Application
The system components must be used exclusively in accor-
dance with their intended use. For further applications, plea-
se contact the manufacturer or an authorised dealer.
Installation
These instructions are aimed at experts and safety-
conscious and/or qualified personnel with knowledge of
the electrical and mechanical installation of drives and
control systems.
Mounting Material
The required fixing materials must be matched to the load
that occurs.
Crush and Shear Points
In order to prevent injury,
Crush and Shear Points
bet-
ween movable and fixed components of windows, louvre
windows and skylights
up to an installation height of
2.5 metres above the floor
, must be protected against
pinching
by suitable measures. For example, this can be
achieved by means of contact or non-contact anti-trap
safety devices that bring the movement to a standstill when
touched or interrupted by a person. A warning sign on the
opening element must clearly indicate this.
Routing Cables and Electrical Connection
The laying or installation of electric cables and connections
may only occur through approved specialist companies. Ne-
ver operate the drives, Control Units, operating elements
and sensors on operating voltages and connections cont-
rary to the specifications of the manufacturer.
he planning and calculation of the cab-
le network is the responsibility of of the
building owner, their designated agents
or the commissioned installer and must
be carried out in accordance with the
statutory regulations.
When mounting and connecting the
system components, the product specific
assembly and installation instructions, as
well as the connection diagram of the
LSF 7000
Control Unit, must be ob-
served.
Both installations are to observe all relevant regulations, in
particular:
• VDE 0100 erection of power installations up to 1000 V
• VDE 0815 installation cables and wires
• Model Pipeline Installation Guideline (MLAR)
• Elevator Directive (ARL).
n
ote
n
ote
The main power line of the Control Unit must
be secured separately by the customer and
provided with all pole isolators. After the
opening of the system housing, live compo-
nents are exposed. The system must be dis-
connected from the mains supply and battery
voltage before any work is carried out on the
Control Unit.
The types of cable, cable lengths and cross-sections are
in accordance with the manufacturers‘ technical data. If
necessary, the cable types must be agreed with the res-
ponsible local authorities and energy supply companies.
Low-voltage lines (24 V DC) must be laid separately from
high-voltage lines. Flexible cables may not be flush- moun-
ted. Freely suspended cables must be equipped with tension
relief devices.
Clamping points must be checked for tightness of screw
connections and cable ends. The accessibility of the junc-
tion boxes, terminal points and external drive controls for
maintenance work must be ensured.
Cables must be laid in such a way that they
are not sheared off, twisted or bent during
operation. It is recommended to carry out an
insulation measurement of the line network of
the system and to document it.