22
RWA Control Unit
LSF 7000
C
ontrol
anD
r
elease
u
nits
Plug-in card 7xPSB
REL 65 (Relais)
Part.-No.:
650200
Application:
Plug-in card for Control Units
LSF 7000
with relay
for transmitting the „EMERGENCY OPEN“ signals
„fault“.
Operating voltage:
24 V DC
Ambient temperature
-5°C … + 40°C
range:
Housing:
without (assembled circuit board)
Dimensions (BxHxD):
20 x 40 x 13 mm
Potenzialfreier Kontakt:
1x Change-over switch, max. 48 V / 1A
Connection terminals:
3x 1,5 mm² (rigid wire)
Feature / Equipment:
• Connector for plugging the relay card onto the motherboard.
04
Connection: Plug-in card 7xPSB in
LSF 7000
1
1
1
5
71
72
1
2
3
1
2
3
BUS-Modul
USB
1
2
3
4
(F1)
(1/2 = Notstromversorgt)
7xPSB
24 V DC
(F2)
+
-
+
-
External Power Supply (7xPSB)
The connection for external devices is used to supply power
to devices, e.g. signal transmitters (siren). This connection has two out-
puts, one of which is supplied with emergency power. The signal trans-
mitters can be connected via the potential-free contacts of the REL65 for
“RWA alarm” and / or “fault” can be controlled.
n
ote
The siren is switched off by pressing the
„CLOSE RESET“ button in the HSE button or on
the motherboard of the
LSF 7000
.
Potential-free Contact for e.g. GLT / Elevator system
The potential-free relay contacts of the two REL65 can optionally be used
to forward the signals to a customer’s BMS.
Lift control system
The fire Control Unit according to DIN EN 81-73 is connected to the
lift system via the potential-free contact of an additional relay REL 65
(Part.-No.:
650200
) in the
LSF 7000
.
The REL 65 is plugged onto the terminals of the first slot of the
control board (alarm triggering / EMERGENCY OPEN).
The signal for the „extended static fire control” is taken directly from
the potential-free contact in the base of the smoke detector at the main
destination stop (see connection in chapter “Smoke detector in the main
evacuation level”).
n
ote
If the fire control is used, no siren can be connec-
ted to the alarm relay of the
LSF 7000
!
Part.-No.:
683256
Application:
Plug-in card for the
LSF 7000
Control Unit to tap
the 24 V DC control voltage for external consumers.
Rated voltage:
24 V DC
Ambient temperature -5°C … + 40°C
range:
Output Current:
0,5 A
Housing:
without (assembled circuit board)
Dimensions (BxHxD): 20 x 32 x 13 mm
Connection terminals: 4x 1,5 mm² (rigid wire)
Voltage tap:
2 terminals 24 V DC emergency power supply
2 terminals 24 V DC mains voltage
Attention:
The current consumption for external consumers must
be taken into account when designing the total current
requirement.