RWA Control Unit
LSF 7000
Check points
OK
Not
OK
N / A
Completeness and visual inspection of the installation
according to the equipment directory.
Smooth running and leak-proof smoke exhaustion systems.
Visual inspection Control Unit.
Intended use of the system.
Mains voltage at Control Unit and charging voltage (27,6 V).
Connection of the protective conductor.
Function ventilation button / ventilation switch.
Function additional devices (e.g. thermostat).
Activating / resetting the system on the HSE button, including displays.
Complete opening of the smoke exhaustion system <60s in case of alarm.
Function of the extended static fire control.
Activating via FAS control.
2.
3.
4.
1.
6.
7.
8.
5.
10.
11.
12.
9.
14.
15.
13.
Signal transmission to / from lift control (inform operating personnel!).
Function of the sirens.
Function-preserving cleaning performed.
Test badge attached.
Information and warning signs available.
16.
17.
18.
20.
21.
19.
Battery voltage / installation date of the battery (replace every 4 years!).
Air quality meter function.
Activation of the system by the smoke detector(s) including displays.
Maintenance timer active / reset.
22.
Function of static fire control.
m
aintenanCe
07