23
RWA Control Unit
LSF 7000
C
ontrol
anD
r
elease
u
nits
Control of FAS
A RWA alarm can also be activated via a potential-free contact of a FAS.
To monitor the line between the FAS and the
LSF 7000
Control Unit, a
FACP module (Part.-No.
670053
) is installed in the FAS and connected to
the terminals of the smoke detector line.
FACU – Connector Module
Part.-No.:
670053
Application:
Module for automatic triggering of the EMERGENCY
OPEN function of a
LSF 7000
via a potential cont-
act of the fire alarm system.
Operating voltage:
24 V DC
Standby current consumption: <10 mA
Ambient temperature range:
0 ... +40 °C
Housing:
without
(assembled
circuit
board)
Dimensions (BxHxD):
27 x 19 x 13 mm
Connections:
Screw terminals 1,5 mm²
(rigid
wire)
FACU contact:
Normally open contact (NO)
on
alarm
triggering
Feature / Equipment:
• Connection to the detector line input, line monitoring between
Control Unit and module.
04