34
RWA Control Unit
LSF 7000
i
nStaLLation
S
tep
2:
C
onneCtion
of
the
s
moke
DeteCtorn
anD
b
reak
-g
lass
u
nits
Connection of the automatic and manual smoke detectors / Break-glass units (HSE) / FACU
Instead of a smoke detector, a connection module
(external NO contact) for EMERGENCY OPEN from an
external fire alarm system (FAS) can also be connected
to terminal 1 /22.
Connect the device whilst it is voltage-free! Switch off
the power supply and secure it against being switched
on again!
!
!
The cables must be laid in accordance with the current
legal regulations. The terminal cross-section for connec-
ting the detectors is max. 1,5 mm², minimum 0,5 mm².
The connection of the manual and automatic smoke de-
tectors is monitored for line faults. Therefore, both the
last smoke detector and the last manual Control Unit
(HSE) in the line must be equipped with a 10kΩ resistor
(RE). If the fire alarm line is not used, attach the 10 kΩ
resistor to terminal 1/22 (smoke alarm line) or terminal
1/13 (manual alarm line) in the Control Unit. If not, the
yellow display “
S
” indicates a fault.
i
nStaLLation
S
tep
2:
c
onnection
of
the
AutomAtic
And
mAnuAl
smoke
detectors
/
b
reAk
-
glAss
units
(hse)
20 a
10 a
5 a
2,5 a
05
1
22
1
2 3 4 5
frei
Kabellänge
max. 400 m
Kontakt
von BMZ
BMA
BMZ-
Anschaltmodul
Art.-Nr.: 670053
IN
CO
M
IN
COM
OUT
OUT
COM-
OUT+
IN+
IN+
IN+
OUT+
OUT+
COM-
COM-
IN
COM
OUT
10 kΩ
max. 10 Stück
max. 400 m
A
S
B
12
34
LSF7000
+ -
7xPSB
1
1
1
5
71
72
- + - -
+ -
A
Z
A
Z
1 32 33 35 36 37
1 22
1 13 14 15 16 17 18 19
- +
OK
R
E
11
10
9
8
7
6
5
4
3
2
1
R
E
im letzten Melder der
Linie einsetzen.
Beim Einsatz BMZ-Anschalt-
modul den
R
E
entfernen.
Werden keine Rauchmelder und kein BMA-Modul
angeschlossen, zwischen Klemme 1 / 22
einen 10 kΩ-Widerstand einsetzten.
Falls Klemmen 1 / 13 / 14 / 15 / 16 / 17 / 18 / 19
nicht belegt sind, zwischen Klemme 1 / 13
einen 10 kΩ-Widerstand einsetzten.
Klemmen
LSF7000
Option:
BMA oder
Rauchmelder
R
E
entfernen.
R
E
1
13
14
15
RD
GN
YE
16
18 19
1 2 3 4 5 6 7 8 9 10 11
Klemmen LSF7000
NOT-
AUF
NOT-
ZU
OK
Anzeigen
Taster
NOT-
AUF
Klemmen HSE
OK
R
E
11
10
9
8
7
6
5
4
3
2
1
Smoke detector
with relay in base
Ø 100
50
Insert a 10 kΩ-resistor between terminal 1 / 22
if no smoke detectors and no FAS module are
connected.
If terminals 1 / 13 / 14 / 15 / 16 / 17 / 18 / 19
are not used, insert a 10 kΩ resistor between
terminals 1 / 13.
Terminal
LSF7000
Option:
FAS or
smoke detector
EMERGENCY
OPEN
EMERGENCY
CLOSE
Cable length
max. 400 m
Contact
from FACU
max. 10 pieces
max. 400 m
Insert
RE
in the last detector
of the line. When using the
FACU connection module,
remove the
RE
.
Remove
RE
free
EMERGENCY
OPEN
Display
Button
Terminals HSE
Terminals LSF7000
FACU
Connector module
Part No.: 670053