15
RWA Control Unit
LSF 7000
Optical Smoke Detector
Point smoke detector with base tested according to EN 54-7.
Part.-No.:
531520
Optical smoke detector with base
- for direct ceiling mounting
Part.-No.:
511232
Mounting bracket
for optical smoke detector
for shaft wall mounting
Part.-No.:
531526
Optical smoke detector with base and relay
- main evacuation level
!
03
Project Planning Proposal
A smoke detector on the shaft ceiling without console
A smoke detector with console below the cabin floor level
For shaft heights of more than 10 metres,
the distance between 2 smoke detectors must not exceed 10 metres
Description
The smoke detectors work according to the optical scattered
light principle without radioactive compounds. They are buil-
ding products tested according to DIN EN 54-7. The proof of
usability under building law is the declaration of performance
of the respective manufacturer and the abZ / aBG of the
L
iFt
-
S
moke
-F
ree
Systems.
Project planning smoke detector arrangement
The primary goal of saving human lives is at the forefront of
the project planning of the smoke detectors in the elevator
shaft. If applicable, the requirements of the combined „ge-
neral building supervision approval“ (abZ) with a „general
type approval“ (aBG), as well as DIN VDE 0833-2 and the
fire protection concept, can be met with the following pro-
ject planning proposal.
s
moke
detection
in
e
levAtor
s
hAft
The conditions of the Fire Protection Authority
are to be adhered to as a matter of principle.
The locations of the smoke detectors are to
be determined according to the fire protection
concept, project planning or in coordination
with the site management. Please consult
the manufacturer if specific problems are not
dealt with in sufficient detail in the operating
instructions.
n
ote
max. 10 m
max. 10 m
max. 10 m
max. 10 m
max. 10 m
max.
10 m
Picture:
531520
or
531526
Picture:
511232
i
nDiviDual
C
omPonents
(D
esCriPtion
, P
rojeCt
P
lanning
, a
ssembly
)
Summary of Contents for Lift-Smoke-Free LSF 7000