Mounting instruction
lindab | we simplif y const ruct ion
Sliding
dampers
SKMTR
SKPTR
Библиотека СОК
Page 1: ...Mounting instruction lindab we simplify construction Sliding dampers SKMTR SKPTR...
Page 2: ...ample min 2 1 m above the floor Connecting conduits must be suspended so that the damper is not exposed to destructive forces These can cause the damper to jam or stick Example of horizontal installat...
Page 3: ...olenoid valve on the damper to the machine EMI 04 is connected to 400 V and supplies 24 V AC to the solenoid valve Control signal from light sensor In light sensor EMI 02 a circuit is closed when the...
Page 4: ...sensor that is to be installed on the power cable to the governing machine is connected to the control unit Commissioning Check that the damper blade moves easily must be performed after mechanical in...
Page 5: ...SPZZ 1 Cylinder 2 Connection 3 Sealing housing 4 Throttle valves A Closing B Opening 5 Solenoid valve 6 Compressed air supply 6 mm 7 Cable contact 8 Solenoid 9 Screw for manual operation of valve 10...