Figure 22: Switch for operating time
[S8]
Operating time
Default value: depending on the order
Setting range: 9 steps (refer to table)
Table 14:
Operating times for 90° in [s]
Switch [S8]
Step
SGM/SGMR 14.1
SGM/SGMR 12.1
SGM/SGMR 10.1
SGM/SGMR
04.1/05.1/07.1
–
275
90
1)
63
1)
1
–
206
63
1)
45
1)
2
345
150
45
1)
32
1)
3
240
103
32
22
4
175
75
22
16
5
120
52
16
11
6
95
41
11
8
7
68
30
8
5.6
8
48
20
5.6
4
9
impermissible switch position
0
Motor is operating in stepping mode
1)
Setting via software parameters (AUMA CDT)
Motor speed and thus actuator operating time can be modified by means of the
software parameters described below. Contrary to operating time setting using switch
[S8], setting via software parameter offers the following additional possibilities:
●
Different motor speeds for operation modes Local and Remote
●
Adjustable motor speed setting (operating times)
●
Motor speed setting (target speed) for operation mode Remote by an external
signal (fieldbus command)
Setting parameters
Condition: Switch [S5] is in position ON (software mode).
Device configuration
Motor speed
Speed LOCAL
Speed REMOTE
Speed fieldbus
Description of parameters:
Speed LOCAL
Output speed for operation via local controls (operation mode Local); Setting range:
linear between 0 – 100 % of max. motor speed; Default value = 50.0 %
30
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Commissioning (basic settings of controls)
Profibus DP