Figure 18: Switch [S5] = Hardware/software mode
Table 8:
Switch [S5] functions
Hardware mode (factory setting on delivery)
Settings of switches [S2] through [S4] and [S6] through [S10] are valid. The values
cannot be changed via AUMA CDT software.
OFF
(1)
Software mode (sliding switch at white dot)
Settings of switches [S2] through [S4] and [S6] through [S10] are NOT relevant.
Settings are defined via software parameters.
ON
(0)
10.3.
Type of seating: set
Valve damage due to incorrect setting!
→
The type of seating setting (limit or torque seating) must match the selection for
the valve.
→
Only change the setting with prior consent of the valve manufacturer.
Setting via switches
Condition: Switch [S5] in position OFF (hardware mode).
Figure 19: Switches for type of seating
[S9]
End position OPEN
[S10] End position CLOSED
Table 9:
Function of switches [S9], [S10]
Limit seating, sliding switch at white dot
ON
Torque seating
OFF
26
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Commissioning (basic settings of controls)
Profibus DP