Switch position [S2]: ON = sliding switch at white dot (pin 1)
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Profibus DP
DP1 slave address
Default value:
126
Setting range:
0 ... 126
10.6.
Termination resistor: connect
✔
This setting is only required if the actuator is the last fieldbus device.
✔
The termination resistor can only be set via switch [S1] and not via the software.
→
Switch on the termination resistor for channel 1 using switch [S1] (standard).
Information: As soon as the termination resistors are switched on, the
connection to the next fieldbus device (to XK3) is automatically interrupted to
avoid multiple terminations.
Table 13: Switch [S1] functions
Fieldbus termination OFF; sliding switch at white dot (pin 1)
(delivery state)
OFF
Fieldbus termination ON
ON
10.7.
Operating time: set
Operating time is defined by the motor speed.
Setting via switches
Switch [S8] is used to change the motor speed and thus the actuator operating time.
The preset operating time is valid for both operation modes (Local and Remote).
Condition: Switch [S5] is in position OFF (hardware mode).
29
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Profibus DP
Commissioning (basic settings of controls)