Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Type of seating
End position CLOSED
End position OPEN
Default value:
Limit
Setting values:
Limit
Limit seating in end positions.
Torque
Torque seating in end positions.
10.4.
Torque switching: set
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Once the set tripping torque is reached, the controls automatically switch off the
actuator (overload protection of the valve).
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 20: Switches for tripping torque
[S6]
Tripping torque in direction OPEN
[S7]
Tripping torque in direction CLOSE
Default value: depending on the order
Setting range: in 8 steps (refer to tables), linear from 40 – 100 % of the maximum
tripping torque.
Table 10:
Tripping torques [Nm]
Switch steps
SGM/SGMR
14.1
SGM/SGMR
12.1
SGM/SGMR
10.1
SGM/SGMR
07.1
SGM/SGMR
05.1
SGM/SGMR
04.1
–
400
200
100
50
25
0
880
400
200
100
50
25
1
880
500
240
120
60
30
2
1,100
550
280
140
70
35
3
1,300
650
320
160
80
40
4
1,500
700
360
180
90
45
5
1,750
800
400
200
100
50
6
27
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Profibus DP
Commissioning (basic settings of controls)