Speed REMOTE
Output speed in operation mode Remote for setting the
Speed fieldbus
=
Internal
parameter; Setting range: linear between 0 – 100 % (0 % = min. motor speed, 100
% = max. motor speed); Default value = 50.0 %
Speed fieldbus
=
External
In operation mode Remote, the output speed is defined via fieldbus.
=
Internal
In operation mode Remote, the output speed is not defined via fieldbus but by means
of the
Speed REMOTE
software parameter.
Table 15:
Example values of type range settings SGM/SGMR 04.1/05.1/07.1/10.1
SGM/SGMR 10.1
SGM/SGMR 04.1/05.1/07.1
Operating time
Output drive
[s]
Speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
Operating time
Output drive
[s]
Speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
81
133
0.0 %
52
133
0.0 %
32
338
10.0 %
22
314
9.0 %
22
491
17.0 %
16
431
14.0 %
16
675
26.0 %
11
627
23.0 %
11
928
40.0 %
8
863
34.0 %
8
1,350
57.0 %
5.6
1 232
52.0 %
5.6
1,929
85.0 %
4
1,725
75.0 %
4.8
2,250
100.0 %
3.1
2,250
100.0 %
Table 16:
Example values of type range settings SGM/SGMR 12.1/14.1
SGM/SGMR 14.1
SGM/SGMR 12.1
Operating time
Output drive
[s]
Speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
Operating time
Output drive
[s]
Speed
Motor
[rpm]
Output speed via parameter:
Speed LOCAL
Speed REMOTE
or via fieldbus:
(
Speed fieldbus
=
External
)
–
–
0.0 %
275
133
0.0 %
–
–
2.0 %
206
186
2.0 %
345
1.1
6.0 %
150
255
6.0 %
240
1.6
11.0 %
103
371
11.0 %
175
2.2
18.0 %
75
510
18.0 %
120
3.2
29.0 %
52
742
29.0 %
95
4.0
38.0 %
41
928
38.0 %
68
5.6
55.0 %
30
1,299
55.0 %
48
8.0
81.0 %
20
1,856
81.0 %
–
–
100.0 %
17
2,250
100.0 %
10.8.
Cover to controls: close
1.
Clean sealing faces of housing and cover.
2.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3.
Check whether seal is in good condition, replace seal if damaged.
31
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Profibus DP
Commissioning (basic settings of controls)