10.
Commissioning (basic settings of controls)
To prevent valve damage and disturbances during commissioning, the basic settings
of controls must be verified prior to electrical actuator operation (motor operation)
and adapted in compliance with the requirements of both valve and application.
Basic settings of controls comprise:
●
Setting the type of seating
●
Setting the torque switches
●
Setting the fieldbus address (slave address)
●
Setting the termination resistor
●
Setting the operating time
To perform basic settings, proceed as follows:
1.
via switches (directly at the device);
For switch setting, open controls cover.
2.
via AUMA CDT software (accessories);
By connecting a PC, laptop or PDA.
Also refer to <AUMA CDT software (accessories)> chapter.
3.
by means of commands via fieldbus;
(Except the termination resistor – this item can only be selected via a switch
within the device.)
For fieldbus configuration, please also refer to the Manual (Device integration
Fieldbus).
Please also refer to <AUMA CDT software (accessories)> chapter for further settings.
10.1.
Cover to controls: open
The cover to the integral controls must be opened to perform the following settings
(options).
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Disconnect device from the mains before opening.
→
Loosen 4 screws and remove cover [1] to controls.
10.2.
Setting via hardware (switches) or via software
The switch [S5] position determines whether the hardware settings (switches) or the
software settings (via AUMA CDT software) are currently active.
25
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Profibus DP
Commissioning (basic settings of controls)