![AUMA SGM 04.1 Operation Instructions Manual Download Page 10](http://html1.mh-extra.com/html/auma/sgm-04-1/sgm-04-1_operation-instructions-manual_3016504010.webp)
5.
Assembly
5.1.
Mounting position
The product described in this document can be operated without restriction in any
mounting position.
5.2.
Mount actuator to valve
The actuator is mounted to the valve using a coupling.
5.2.1.
Overview on coupling variants
Design principle
Figure 6: Coupling variants
[1]
Bore with keyway
[2]
Square bore
[3]
Bore with two-flats
[4]
Valve shaft
[5]
Output mounting flange (size 12.1/14.1)
Application
●
For valve attachments according to EN ISO 5211
●
For rotating, non-rising valve stem
5.2.2.
Mount actuator (with coupling)
Unbored couplings or couplings with pilot bore must be machined to match the valve
shaft prior to mounting the actuator to the valve (e.g. with bore and keyway, two-flat
or square bore).
Assemble valve and actuator in the same end position. As standard, the actu-
ator is supplied in end position CLOSED.
→
Recommended mounting position for butterfly valves: End position CLOSED.
→
Recommended mounting position for ball valves: End position OPEN.
Assembly steps
1.
If required, move actuator in same end position as valve using the handwheel.
2.
Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
3.
Apply a small quantity of grease to the valve shaft [2].
10
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Assembly
Profibus DP