Activate operation mode LOCAL:
→
Hold down push button [2] for approx. 3 seconds until right indication light is
blinking in blue.
Information
If the local controls are not provided on site, it is possible to connect an external
control module. The setting is then performed in the same way as described below.
11.3.1.
End position CLOSED: set again
Activate setting mode "end position setting":
1.
Press push button [2] – hold down and press push buttons [1] and [3] at the
same time.
➥
Now, the right indication light is blinking faster (5 Hz).
Set end position CLOSED:
2.
Use crank handle/handwheel or push button [3] for running the actuator to end
position CLOSED. (Actuator runs at reduced output speed in setting mode.)
3.
Press push button [2] – hold it down and press push button [3]. Hold both push
buttons down until the right indication light is blinking alternately in yellow and
blue (default).
➥
If the right indication light is blinking in yellow/blue, end position CLOSED setting
is complete.
36
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Commissioning (basic settings at actuator)
Profibus DP