Temperature Rating - Units are considered acceptable for use in a
maximum ambient of 40°C (104°F).
For Pluggable Equipment - The socket-outlet shall be installed near the
equipment and shall be easily accessible.
For normal operation of the UPS (at full load UPS), it is required to keep
the unit below a maximum altitude of 3000m.
Operation
Do not disconnect the mains cable on the UPS system or the building
wiring outlet (shockproof socket outlet) during operations since this would
cancel the protective earthing of the UPS system and of all connected
loads.
The UPS system features its own, internal current source (batteries). The
UPS output sockets or output terminals block may be electrically live even
if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter
button to disconnect the mains.
Prevent no fluids or other foreign objects from entering the inside of the
UPS system.
To reduce the risk of fire, connect only to a circuit provided with X (in
ampere, refer to the table below) maximum branch circuit overcurrent
protection in accordance with the National Electrical Code, ANSI/NFPA
70 and the Canadian Electrical Code, Part I, C22.1.
Model
X
OL1000LV, OL1500LV, OL2000LV
20A
OL3000LV
40A