UPS User Manual
36
Bypass Frequency Range Setting
Display: 08
Display: HS
Parameter 2: Acceptable high frequency
point and acceptable low frequency point
for Bypass mode.
Press the Up or Down
key to adjust the values.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss
point from 61Hz to 65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss
point from 45Hz to 49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss
point from 55Hz to 59Hz(Default: 57.0Hz)
Enable/Disable Programmable
Outlets
Display: 09
Parameter 2: Enable or disable
programmable outlets.
ENA:
Enable Programmable outlets
DIS:
Disable Programmable outlets (Default)
Programmable Outlet Backup
Time Setting
Display: 10
Parameter 2: Backup time limits for
programmable outlets.
0-999:
setting the backup time limits in
minutes from 0-999 for programmable
outlets which connect to non-critical devices
on battery mode. (Default: 999)
Parameter 1 & Interface Display
Parameter 2 Description
Summary of Contents for OL1000LV
Page 1: ...OL1000LV OL1500LV OL2000LV OL3000LV Professional Online UPS UL Listed User Manual...
Page 18: ...UPS User Manual 8 This Page Intentionally Left Blank...
Page 22: ...UPS User Manual 12...
Page 29: ...Chapter 2 Hardware Setup 19...
Page 36: ...UPS User Manual 26 This Page Intentionally Left Blank...