Autonomy Limitation Setting
Display: 11
Parameter 2:
Backup time on battery
mode
for general outlets.
0-999:
Set the backup time (in minutes) from
0-999 for general outlets on battery mode.
DIS:
Disable the autonomy limitation and the
backup time will depend on battery capacity.
(Default)
Note:
When setting as “0”, the backup time
will be only 10 seconds.
Battery Total AH setting
Display: 12
Parameter 2:
Battery total AH
of the UPS.
7-999:
Set the battery total capacity from 7-
999 in AH. Please set the correct battery
total capacity if external battery pack is
connected.
Maximum Charger Current Setting
Display: 13
Parameter 2: Charger maximum current.
For low voltage model with 24/36/48VDC
1/2/4/6/8:
Set maximum charger current to 1/
2/4/6/8 Ampere. (Default: 2A)
For low voltage and high voltage model with
72/96VDC
1/2/4/6/8:
Set maximum charger current to 1/
2/4/6/8 Ampere. (Default: 2A)
Note: Please set the appropriate charger
current based on battery capacity used. The
recommended charging current is
0.1C~0.3C of battery capacity as following
table for reference.
Warning:
Setting the current too high may
cause damage to the device.
For the recommended charger current,
please refer to
Parameter 1 & Interface Display
Parameter 2 Description
Summary of Contents for OL1000LV
Page 1: ...OL1000LV OL1500LV OL2000LV OL3000LV Professional Online UPS UL Listed User Manual...
Page 18: ...UPS User Manual 8 This Page Intentionally Left Blank...
Page 22: ...UPS User Manual 12...
Page 29: ...Chapter 2 Hardware Setup 19...
Page 36: ...UPS User Manual 26 This Page Intentionally Left Blank...