Chapter 4. LCD/Button Operations
35
Enable/Disable Bypass when UPS
is off
Display: 06
Parameter 2: Enable or disable
Bypass
function.
You may choose the following two options:
ENA:
Enable bypass
DIS:
Disable bypass (Default)
Bypass Voltage Range Setting
Display: 07
Display: HS
Parameter 2: Acceptable high voltage
point and acceptable low voltage point
for Bypass mode.
Press the Up or Down
key to adjust the values.
HLS:
Bypass high voltage point
For 100/110/115/120/127 VAC models:
120-140:
setting the high voltage point range
of parameter 3 to between 120Vac and
140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 100/110/115/120/127 VAC models:
85-115:
setting the low voltage point range of
parameter 3 to between 85Vac and 115Vac.
(Default: 85Vac)
Parameter 1 & Interface Display
Parameter 2 Description