15
•
REV. TIME
(Reversal-Time)
0,1 up to 2,0 sec.
Pre-setting: 0,5 sec.
Delay-time before changing moving-direction.
•
2ND Time
0 up to 60 sec.
Pre-setting: 0 sec.
With activation of the "2nd time" the function of quick closing
after crossing the light barrier can be realized in the
"automatic closing" mode. Instead of the adjusted open time
the 2nd time is used as the new open time after crossing
the light barrier.
•
Relay
Light
MOD 1,2,3,4 or 5
Pre-setting: MOD 1
Relay output to control a light, a warning light or a brake at
the gate.
MOD 1: Continuous light funct. as long as gate is in motion
MOD 2: Light control after opening-instruction for 3 min.
MOD 3: Brake function, relay switched if gate stops
MOD 4: Failure light, lights so long as the failure is present
MOD 5: Failure light, like MOD 4 however with 20 sec.
switch -off delay
•
EDGE CL
(Safety contact edge closing direction)
MOD 1 or 2
Pre-setting: MOD 2
This parameter specifies the reaction of the controller if the
safety contact edge is activated in the closing movement.
MOD 1: STOP plus short reversion 1,5 sec.
MOD 2: STOP plus full reversion
•
EDGE OP
(Safety contact edge opening direction)
MOD 1 or 2
Pre-setting: MOD 1
This parameter specifies the reaction of the controller if the
safety contact edge is activated in the opening movement.
MOD 1: STOP plus short reversion 1,5 sec.
MOD 2: STOP plus full reversion
•
LIGHT B. CL
(Light barrier closing movement)
MOD 1 or 2
Pre-setting: MOD 2
This parameter specifies the reaction of the controller if the
light barrier is interrupted (closing movement).
MOD 1: STOP plus short reversion 1,5 sec.
MOD 2: STOP plus full reversion
•
BRAKE:
MOD 1 or 2
Pre-setting: MOD 2
This parameter specifies how the motor-brake is controlled.
MOD 1: Relay is activated if motor stands
MOD 2: Relay is activated if motor runs
MOD 3: Relay is activated for 3 sec. if motor stands
MOD 4: Relay is activated for 3sec. if motor runs
•
IMPULS MOD
MOD 1 or 2
Pre-setting: MOD 1
Specifies the function of the impulse-input.
MOD 1: open/stop/close/stop ...
MOD 2: open/close/open ...
•
TIME SWIT.
(Time Switch)
MOD 1 or 2
Pre-setting: MOD 1
Specifies the function of the time switch.
The operation of the gate is at anytime possible because
the clock only prevents automatic closing.
MOD 1: Opening of the gate by opening-button, after that
the clock keeps the gate open.
MOD 2: Opening of the gate by clock, after that the clock
keeps the gate open.