TD 92579EN
15 February 2012 / Ver. H
Installation and Operation Manual
IP-DECT Base Station & IP-DECT Gateway (software version 5.0.x)
104
2
Select the Encryption check box.
NOTES:
a) When selecting or clearing the Encryption check box, it may take
up to a couple of minutes until the IMS3/Unite CM is fully
operational..
b) The IMS3/Unite CM support for encryption is depending on the
IMS3/Unite CM software version.
3
Click "OK".
8.7.2
Device Management
If a specific Device Manager (for example IMS3) is to be used in the IP-DECT system, enter
the IP address to the Device Manager following the steps below. To set the Master to
search for an existing Device Manager on the network, go to
8.7.3
Service Discovery
on
page 104.
1
Select UNITE > Device Management.
NOTE: To access the
Device Management
tab, the Master mode has to be activated,
see
8.5.13
Select Mode
on page 94.
2
Enter the address to the Device Manager in the
Unite IP Address
text field.
The IP address for the Device Manager that the Master is currently connected to is
shown under
Active Settings
.
3
Click "OK".
8.7.3
Service Discovery
If no Device Manager (for example IMS3) has been selected to be used in the IP-DECT
system, see
8.7.2
Device Management
on page 104, then the Master will automatically
search for an existing Device Manager on the network. To set the Master to search in a
specific domain on the network or to stop the search, follow the steps below.
1
Select UNITE > Service Discovery.
NOTE: To access the
Service Discovery
tab, the Master mode has to be activated, see
8.5.13
Select Mode
on page 94.
2
Do one of the following:
• To stop the Master to search for a Device Manager, select the
Disable
check box.
• To set the Master to search for a Device Manager in a specific domain on the
network, enter the domain id in the
Domain ID
text field. The domain id must be
the same as the one entered in the Device Manager.
3
Click "OK".
8.7.4
Send Status Log
It is possible to send alarm and event reports to the Unite system. For example directly to
the ESS fault handler or to the UNA (Unite Node Assistant) which in turn forwards the
alarm event according to distribution lists.
1
Select UNITE > Status Log.
2
Enter the address to the server where the Status Log should be sent in the
Unite IP
Address
text field.
3
Enter the Resource Identity/Service in the
Unite Resource Identity
text field. If this
field is left empty then the default will be UNA (Unite Node Assistant).