5 - 15
Figure 5-8
Tapping an input or output key opens a pop-up window with more detailed
information.
The I/O screens show the state of each input or output. These are shown green when they
are active. Low = 0Vdc and high = +24Vdc.
The detailed view shows the input or output’s dependencies by listing the component
identifications for the selected circuit.
In the example above:
•
Load Bank Module output OP37 drives relay K137 which in turn drives the load step
contactor K37.
•
K37 is 465kVAr inductive load step rated at 690V/50Hz.
•
The load step fuse is F37 rated at 500A.
The location of each component is also detailed along with the Froment drawing number
which shows the circuit.
Maintenance & Troubleshooting