4 - 30
Running the automatic sequence
To run the test sequence press the
I key. The green LED on the Hand-held will begin to
flash to indicate that the test sequence is running and the status bar will indicate the
current stage of the test.
Figure 4-23
Automatic test sequence display
•
Press F1(PAGE) to step through the different views of the instrumentation provided by
the Test pages (See “The Test Pages” on page 4-18 for more details).
•
Press the
I key a second time to trigger load correction. See “Using load correction” on
page 4-23 for more details on how load correction works.
•
Pressing F2 (MANUAL), F3 (EDIT TEST) or F4 (SETTINGS) will pause the sequence at
its current load value.
•
Resume a paused test sequence by going back into Automatic mode and pressing the
I key. The sequence will restart with the time remaining for the load step.
•
The
+ and - keys can be used to adjust the percentage load applied as the sequence is
running. Press the I key to apply the new load. This can be useful if you need to reduce
the load because the preset load is causing the generator to stall.
Press
O at any time to stop the test sequence, reject the load and start the fan delay.
If the Ramp Down on Reject function is enabled (see page 4 - 16) the load will ramp down
for 12 seconds before the fan delay starts. The Hand-held’s LED will flash to indicate this.
Press
O a second time to reject the load immediately if necessary.
Note: If the “Cyclic Auto
Test” is selected in the
Control Options, then
the test will continue
from step 16 to step 1 in
a constant loop until
O
is pressed to stop the
test.
Hand-held Reference Guide