4 - 9
Hand-held Quick Start
Figure 4-5
Hand-held quick start manual test sequence.
Press the start button on the
load bank control panel. Press F1
(Check) to go to the supply on
test settings page.
If the supply on test settings are
correct, press F4 (TEST) to start
testing the supply.
Settings not correct? Press F2 (NEW). The
voltage and frequency will be measured and
set to the nearest standard values (if there is
no supply they will be set to defaults).
Use the + or - keys (or
F1 PRESET) to adjust
the supply size.
Press F4 (OK) when the
values match those on the
generators rating plate.
Test 1-4 is the first of the
four test instrumentation
pages provided by the
Hand-held.
Select the percentage load required
using the + or - keys.
A pop up will appear show-
ing the adjusted value and
this is also displayed on
the right of the status line.
Apply the load by pressing the I key. The
LED will light, indicating a test in progress.
Press the I key again for load correction.
The status line displays
the elapsed time since the
load was applied.
Press the O key to reject
the load and end the test.
Preselect the percentage load
required for the next load change
using the + and - keys.
Chapter Four