Froment load banks are constructed to suit customers specifications for a particular application. The following
table describes standard equipment for the 8800, but there are many custom options and configurations available.
Please contact Froment sales office for more details.
The data shown is for standard build equipment. Other capacities & voltages are available and the fan details may
also change dependant on specific requirement.
Introducing Froment Load Banks
1 - 17
8800 S
ERIES
Load Bank Specifications
8800
Nominal capacity @ 0.8pf 11kV 50Hz (kVA)
2750
Terminal quantity/phase & size(mm)
1 x M12
Containerised ISO style
(20ft)
Length (mm)
6058
Width (mm)
2438
Height (mm)
2591
Weight, approximate (kg)
20000
Fan(s) - No. x diameter (mm)
2 x 900
Fan poles
4
Fan motor (kW/Ph)
10.5/3
Fan & Control current max (A)
38.4
Total current max - Starting (A)
124
Fan start - Staggered starting for multiple units
DOL
Noise level, dB(A) 50Hz @ 90° (@ 3m)
85
Airflow 50Hz (m³/sec)
14
Fan static pressure 50Hz (Pa)
415
Average air temp Rise 50Hz (°C)
146
Air outlet velocity 50Hz (m/s)
6
Airflow direction
Vertical