38
Rev 2, 18.06.19
Variable
Description
Value
Aroma water input status.
Temperature
0=NO
1=NC
VTC
Fan pause during defrosting.
Evaporator probe temperature displayed
(temp will not be displayed if ESE = 0).
Door switch input status (with door closed).
Temperature
0=NO
1=NC
0=fans not operating
1=fans operating
VTE
PVS
AG
M
Condenser probe temperature displayed
(temp will not be displayed if ESC = 0).
Default
Read
Only
Read
Only
1
0
0
AVA
Fan enablement during aroma.
0=DISABLED
1=ENABLED
0
Fan enablement during cooling.
Alarm notification time delay
for minimum or maximum temperature.
0=DISABLED
1=ENABLED
0=INSTANTANEOUS
0<=OFF
0 min….240 min
AVF
RAT
1
90 min
Enable Humidification.
0=DISABLED
1=ENABLED
U
1
Alarm notification time delay
for minimum or maximum humidity.
0=INSTANTANEOUS
0<=OFF
0 min….240 min
RAU
30 min
VMC
Fans in continuous operation.
If enabled during defrosting they stop if PVS=0.
0=DISABLED
1=ENABLED
0
TSF
Minimum time between cooling shut off and the next
subsequent switch on. It also stops the fans if they are not
enabled for other functions.
0 min…10 min
0 DISABLED
1 min
DEU
Dehumidification mode selection
Separated dehumidification enables hot and cold only for
temperature.
0=COOLING
1=HEATING
2=SEPARATE
DEHUMIDIFICATION
0
Enable Dehumidification.
0=DISABLED
1=ENABLED
DE
1
SYSTEM VARIABLES continued