Chapter 3: Configuration and commissioning
92
2X Series Installation Manual
4. Select Active, and then select YES (to confirm output group activation in case
of an alarm) or NO (to deactivate the output group).
5. Select Delay and enter the required delay in minutes and seconds.
The maximum delay value for sounder, fire routing, and fire protection output
groups is 10 minutes. The maximum delay value for program output groups is
16 minutes and 40 seconds.
6. If required, enter a warning delay (in minutes and seconds) for sounder output
groups in applications using warning tones (second stage sounders).
A warning delay is only observed if the corresponding warning time is also
configured (see “Warning time” on page 97 for more information on this
option). The maximum warning delay value is 10 minutes.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Once a delay has been configured, it must be enabled.
Configured delays are only activated for alarms activated by a detector. Alarms
activated by a manual call point ignore any configured delays.
Configured delays can be enabled or disabled by sensitivity mode programming
(day/night mode), remote equipment by means of a programmed input, or the
user interface delay buttons.
By default, the control panel does not process delays when operating in night
mode. Remember that night mode can be activated by the day/night mode
schedule, the holiday calendar, or by remote equipment. For specific
applications, a delay in night mode can be configured if required. See “Additional
day/night mode settings” on page 42.
Use these options to configure, for example, activation of sounders and fire
routing with 2 minute delay for any zone in alarm in the fire network inside the fire
alarm panel zone range.
Notes
• Global delay options only set the delays of the zones that are enabled to
activate the sounder or fire routing group. For example, if sounders and fire
routing activate for zone 1 with a delay of 10 seconds and for zone 5 with a
delay of 2 minutes, when selecting this option, sounders and fire routing will
activate with the same selected delay after alarms in zones 1 or 5 and will not
activate for all the other zones.
• The Activate for all zones option allows the user to apply the delay to all
zones (including those previously configured not to activate the output group).
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......