Chapter 3: Configuration and commissioning
58
2X Series Installation Manual
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
The commands that can be controlled globally are detailed in Table 24 below.
Event filter
Select the Event filter option to configure the types of events to repeat from other
control panels in the fire network. The control panel always displays alarm and
alert events. Fault and condition reporting may also be selected if required.
To change the Event filter settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Event filter.
3. Select the types of events to repeat.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Command filter
Select the Command filter option to configure the types of commands sent to the
fire network in control panels with the corresponding global controls configured.
The commands that can be configured are shown in the table below.
Table 24: Command filter configuration options
Command
Description
RST
Reset
PnSilen
Panel silence
SND
Sounder start/stop
SND_DLY
Sounder delay (enable delay or cancel active delay)
FR
Fire routing start/stop
FR_DLY
Fire routing delay (enable delay or cancel active delay)
FP
Fire protection start/stop
FP_DLY
Fire protection delay (enable delay or cancel active delay)
D/N_M
Day/night mode change [1]
UKSB
UK school bell on/off
[1] Used to allow control panels within the network to have locally-defined day/night mode
settings. If this setting is not activated, the control panel does not send the day/night mode
change and does not process these commands when received from other control panels in the
fire network.
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......