Chapter 3: Configuration and commissioning
84
2X Series Installation Manual
Type
Description
FRAK1
Fire routing acknowledgement (type 1). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 100 seconds of fire routing activation, the control panel
reports a fire routing fault.
FRAK2
Fire routing acknowledgement (type 2). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 240 seconds of fire routing activation, the control panel
reports a fire routing fault.
FPAK1
Fire protection acknowledgement (type 1). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 100 seconds of fire protection
activation, the control panel reports a fire protection fault.
FPAK2
Fire protection acknowledgement (type 2). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 240 seconds of fire protection
activation, the control panel reports a fire protection fault.
FP_FT
Fire protection fault. Used to indicate remote faults in fire protection
equipment.
FBFSD
FBF sounders disable. The input is configured to interface to remote
FBF equipment to disable or enable sounders.
UKSB
British school class change. Activation activates sounders for school
class change indication.
MSP
Manual call point alarm (sprinkler).
MHA
Manual call point alarm (“hausalarm”).
To enable or disable a control panel input:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Panel inputs, and then select the corresponding input.
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Panel output configuration
Configurable options for control panel outputs are shown below.
Table 47: Configurable options for control panel outputs
Option
Description
Type
Configures the output operation mode
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......