Chapter 3: Configuration and commissioning
2X Series Installation Manual
97
Warning time
Select the Warning time option to configure a warning time for applications with
warning tone requirements (second stage sounders).
Note:
If a warning delay is required, this must be configured separately (see
“Sounder, fire routing, fire protection, and program output group delays” on page
91).
With this option, sounders emit the warning tone for a configured period of time
(the warning time). When the warning time ends, the sounder tone changes to
the evacuation tone (the warning tone continues to sound for the duration of any
configured delay that precedes the evacuation tone). See Figure 24 and
Figure 25 on page 98, below, for examples of delays with and without second
stage requirements.
Note:
The sounder tones are configured in the corresponding device
configuration screen.
There are three configurable time periods, as shown in the table below.
Table 57: Warning time, warning delay, and delay
Time period
Description
Warning time
The time from when the alarm is reported until the sounders activate
the evacuation tone (or the corresponding evacuation tone delay
starts to count down)
Warning delay [1]
The optional delay before the sounders activate the warning tone
Delay [1]
The optional delay before the sounders activate the evacuation tone
[1] To configure these values, see “Sounder, fire routing, fire protection, and program output
group delays” on page 91.
Figure 24: Detector alarm with second stage delay
Warning tone
Evacuation tone
Warning time (or
second stage delay)
Warning delay
Delay
D
et
ec
tor
al
ar
m
R
es
et
Time
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......