Chapter 3: Configuration and commissioning
2X Series Installation Manual
59
To change the Command filter settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Command filter.
A list of available commands that can be configured is displayed.
3. Select all commands to be filtered.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Class B
Select the Class B option to configure your fire network class configuration
(Class A or Class B). The default setting is NO (Class A network configuration).
To change the network class settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Class B.
3. Select YES (for Class B network) or NO (for Class A network).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Communications configuration
TCP/IP
Default TCP/IP settings are shown in the table below. The control panel MAC
address and Host information is also available in this screen if required for
troubleshooting purposes.
Note:
For increased security, we recommend against using Ethernet for remote
connection to the control panel via the Internet.
Table 25: Default TCP/IP settings
Option
Default value
IP address
192.168.104.140
Subnet mask
255.255.255.0
Gateway
0.0.0.0
Port
2505 [1]
[1] If the default port is changed, the port configuration in the configuration utility PC application
must also be updated.
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......