Chapter 3: Configuration and commissioning
2X Series Installation Manual
91
Delay configuration options are shown in the table below.
Table 52: Activation configuration options
Option
Description
Sounders
Configures the activation of sounder groups with zones in alarm. A
warning delay can also be configured if the second stage delay option is
required.
Fire routing
Configures the activation of fire routing groups with zones in alarm.
Fire protection
Configures the activation of fire protection groups with zones in alarm.
Program
Configures the activation of program groups with zones in alarm.
Per zone
Configures the activation of output groups for each individual zone in
alarm. For each zone, a different output group activation delay (including
no activation) can be assigned for each configured output group.
General delays
Configures sounder silence disable time, maximum acknowledge time or
extended fire routing delays, and warning time for second stage sounders
applications.
Sounder, fire routing, fire protection, and program output group delays
Select an output group type option to configure delays (including no activation)
for sounder, fire routing, fire protection, and program output groups for all zones.
These output groups can be configured individually or all output group types at
the same time. All zones are programmed with the same setting: global delay or
no activation.
Configurable options for output group delays are shown in the table below.
Table 53: Configurable options for output group delays
Field
Description
Group_n
Output group selection (all output groups of the type selected or a
single output group of the type selected)
Active
Output group activation (yes or no)
Delay
The delay (in minutes and seconds)
Wrn_Dly [1]
The warning delay (in minutes and seconds)
[1] Sounder output group delays only.
To configure the output group delay:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select the output group type to configure (Sounder, Fire routing, etc.).
3. Select Group_n, and then select ALL (to configure common delay settings for
all output groups of the type selected) or select the output group number (to
configure custom delay settings for a single output group of the type
selected).
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......