Chapter 3: Configuration and commissioning
2X Series Installation Manual
87
Group number
Type
Description
801
EXTIN
Extinguishing device outputs. [1]
971
FR
Fire routing outputs. This group is only available on
control panels with the corresponding fire routing controls.
981
FP
Fire protection outputs. This group is only available on
control panels with the corresponding fire protection
controls.
991
ALARM [2]
Outputs activated when the control panel is in alarm
status.
992
FAULT [2]
Outputs activated when the control panel is in fault status.
993
DIS [2]
Outputs activated when the control panel is in disable
status.
994
TEST [2]
Outputs activated when the control panel is in test status.
[1] Extinguishing output groups are only activated with EN 54 type C alarm confirmation.
[2] These output groups are not configurable.
Configurable options for output groups are shown below.
Table 50: Configurable options for output groups
Option
Description
Group_n
Configures the output group number
Type
Configures the output group type
Control
Enables or disables the output group
[BLANK]
Output description
To configure a default output group:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Output groups.
A list of the available output groups is displayed. Press F3 (Search) to search
by group number. Press F4 (Delete) to delete an output group.
3. Select the output group to configure.
You cannot change the group number or output group type for a default
output group.
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Enter a brief text description for the output group.
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Summary of Contents for 2X Series
Page 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Page 6: ...iv 2X Series Installation Manual ...
Page 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Page 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Page 140: ......