Rated current In
5A (con gurable 0.2A…10A)
Thermal withstand
30A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
25mA…250A(rms)
Current measurement inaccuracy
0.005xIn…4xIn < ±0.5% or < ±15mA
4xIn…20xIn < ±0.5%
20xIn…50xIn < ±1.0%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.1A)
< ±1.0 ° (I
≤
0.1A)
Burden (50Hz/60Hz)
<0.1VA
Transient overreach
<8%
Coarse residual current input (I01)
Rated current In
1A (con gurable 0.2A…10A)
Thermal withstand
25A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
5mA…150A(rms)
Current measurement inaccuracy
0.002xIn…10xIn < ±0.5% or < ±3mA
10xIn…150xIn < ±0.5%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.05A)
< ±1.0 ° (I
≤
0.05A)
Burden (50Hz/60Hz)
<0.1VA
Transient overreach
<5%
Fine residual current input (I02)
Rated current In
0.2A (con gurable 0.2A…10A)
Thermal withstand
25A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
1mA…75A(rms)
Current measurement inaccuracy
0.002xIn…25xIn < ±0.5% or < ±0.6mA
25xIn…375xIn < ±1.0%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.01A)
< ±1.0 ° (I
≤
0.01A)
Burden (50Hz/60Hz)
<0.1VA
AQ-T257
Instruction manual
Version: 2.00
327
© Arcteq Relays Ltd