Resetting characteristics can be set according to the application. Default setting is delayed with 60 ms
and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the operating time
during the release time, function will not trip if the input signal is not activated again during the release
time counting.
Events and registers
The NOV function generates events and registers from the status changes of start, trip and blocked. To
main event buffer is possible to select status “On” or “Off” messages. The NOV function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.11. - 117. Event codes of the NOV function instance 1 – 4.
Event Number
Event channel
Event block name
Event Code
Description
5952
93
NOV1
0
Start ON
5953
93
NOV1
1
Start OFF
5954
93
NOV1
2
Trip ON
5955
93
NOV1
3
Trip OFF
5956
93
NOV1
4
Block ON
5957
93
NOV1
5
Block OFF
6016
94
NOV2
0
Start ON
6017
94
NOV2
1
Start OFF
6018
94
NOV2
2
Trip ON
6019
94
NOV2
3
Trip OFF
6020
94
NOV2
4
Block ON
6021
94
NOV2
5
Block OFF
6080
95
NOV3
0
Start ON
6081
95
NOV3
1
Start OFF
6082
95
NOV3
2
Trip ON
6083
95
NOV3
3
Trip OFF
6084
95
NOV3
4
Block ON
6085
95
NOV3
5
Block OFF
6144
96
NOV4
0
Start ON
6145
96
NOV4
1
Start OFF
6146
96
NOV4
2
Trip ON
6147
96
NOV4
3
Trip OFF
6148
96
NOV4
4
Block ON
6149
96
NOV4
5
Block OFF
In the register of the NOV function is recorded start, trip or blocked “On” event process data. In the
table below is presented the structure of NOV function register content. This information is available in
12 last recorded events for all provided instances separately.
AQ-T257
Instruction manual
Version: 2.00
113
© Arcteq Relays Ltd