U1 Polarity
0:-
1:Invert
-
0:-
U1 ( rst voltage) measurement channel polarity (direction) selection.
Default setting is that positive voltage flow is from connector 1 to
connector 2 and the secondary voltage star point is towards line.
U2 Polarity
0:-
1:Invert
-
0:-
U2 (second voltage) measurement channel polarity (direction)
selection. Default setting is that positive voltage flow is from connector
1 to connector 2 and the secondary voltage star point is towards line.
U3 Polarity
0:-
1:Invert
-
0:-
U3 (third voltage) measurement channel polarity (direction) selection.
Default setting is that positive voltage flow is from connector 1 to
connector 2 and the secondary voltage star point is towards line.
U4 Polarity
0:-
1:Invert
-
0:-
U4 (fourth voltage) measurement channel polarity (direction) selection.
Default setting is that positive voltage flow is from connector 1 to
connector 2 and the secondary voltage star point is towards line.
VT scaling
factor P/S
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary voltage ratio
VT scaling
factor p.u. Pri
-
-
-
IED feedback value, scaling factor from p.u. value to primary voltage.
VT scaling
factor p.u. Sec -
-
-
IED feedback value, scaling factor from p.u. value to secondary
voltage.
U3 VT scaling
factor P/S
U0/SS
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary voltage ratio of voltage channel U3. (Valid only in
2LL+U3+U4 mode)
U3 scaling
factor p.u. Pri
-
-
-
IED voltage channel U3 feedback value, scaling factor from p.u. value
to primary voltage. (Valid only in 2LL+U3+U4 mode)
U3 scaling
factor p.u. Sec -
-
-
IED voltage channel U3 feedback value, scaling factor from p.u. value
to secondary voltage. (Valid only in 2LL+U3+U4 mode)
U4 VT scaling
factor P/S
U0/SS
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary voltage ratio of voltage channel U4.
U4 scaling
factor p.u. Pri
-
-
-
IED voltage channel U4 feedback value, scaling factor from p.u. value
to primary voltage.
U4 scaling
factor p.u. Sec -
-
-
IED voltage channel U4 feedback value, scaling factor from p.u. value
to secondary voltage.
Measurements
Following measurements are available from the measured voltage channels.
Table. 5.2.2. - 24. Per unit voltage measurements.
Name
Range
Step
Description
Ux Volt p.u.
0.00…
500.0xUn
0.01V Per unit measurement from each voltage channel fundamental frequency RMS
voltage.
UxVolt TRMS
p.u.
0.00…
500.0xUn
0.01V
Per unit measurement from each voltage channel TRMS voltage including
harmonics up to 31
st
.
Table. 5.2.2. - 25. Secondary voltage measurements.
Name
Range
Step
Description
Ux Volt sec
0.00…
500.0xUn
0.01V Secondary measurement from each voltage channel fundamental frequency RMS
voltage.
UxVolt TRMS
sec
0.00…
500.0xUn
0.01V
Secondary measurement from each voltage channel TRMS voltage including
harmonics up to 31
st
.
Table. 5.2.2. - 26. Voltage phase angle measurements.
Name
Range
Step
Description
AQ-T257
Instruction manual
Version: 2.00
29