Figure. 5.4.4. - 25. Effect of angle divider when in use and when disabled.
To receive more accurate indication whether the trip was in a compensated or unearthed network
angle divider can divide the area which would be otherwise overlapped between the two network
models. By default the setting is 45 degrees. If the angle is set to zero degrees the divider is disabled.
Real-time info displayed by the function
The IEDs Info-page displays useful information in real time of the state of the protection function either
through relays HMI display or with AQtivate software when connection there is a connection to relay
and Live Edit-mode is activated.
Table. 5.4.4. - 71. Information displayed by the function
Name
Unit
Description
U0> Pick-up setting
V
Required residual voltage on the primary side for the relay to trip.
Detected U0I0 angle ( )
Deg
The angle in degrees between the monitored residual voltage and current
I0 Magnitude
xI0n
Per-unit-value of the monitored residual current
I0 Wattmetric I0xCos( )
xI0n
Wattmetric per-unit-value of the monitored residual current
I0 Varmetric I0xSin( )
xI0n
Varmetric per-unit-value of the monitored residual current
I0 direction now
Unde ned
Forward
Reverse
Detected direction of the residual current.
I0 meas / I0 set now
xI0n
Ratio between monitored residual current and pick-up setting
U0 meas now
%U0n
The measured voltage in the chosen voltage channel.
Expected operating time
s
Displays the expected operating time in case a fault occurs
Time remaining to trip
s
When the relay has picked up and is counting time towards pick-up
AQ-T257
Instruction manual
Version: 2.00
63